• Title of article

    Investigation of heat exchanger inclination in forced-draught air-cooled heat exchangers

  • Author/Authors

    Kennedy، نويسنده , , Ian J. and Spence، نويسنده , , Stephen W.T. and Spratt، نويسنده , , Gordon R. and Early، نويسنده , , Juliana M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    9
  • From page
    413
  • To page
    421
  • Abstract
    The purpose of this study is to determine the influence of inclining the heat exchanger relative to the fan in a forced draught air-cooled heat exchanger. Since inclination increases plenum depth, the effect of inclination is also compared with increasing plenum depth without inclination. The experimental study shows that inclination improves thermal performance by only 0.5%, when compared with a baseline non-inclined case with a shallow plenum. Similarly, increasing plenum depth without inclination has a thermal performance benefit of approximately 1%. The numerical study shows that, as the heat exchanger is inclined, the low velocity core at the centre of the heat exchanger moves to one side.
  • Keywords
    INCLINATION , Forced-draught air-cooled heat exchanger
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2013
  • Journal title
    Applied Thermal Engineering
  • Record number

    1905754