Title of article
Investigation of heat exchanger inclination in forced-draught air-cooled heat exchangers
Author/Authors
Kennedy، نويسنده , , Ian J. and Spence، نويسنده , , Stephen W.T. and Spratt، نويسنده , , Gordon R. and Early، نويسنده , , Juliana M.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2013
Pages
9
From page
413
To page
421
Abstract
The purpose of this study is to determine the influence of inclining the heat exchanger relative to the fan in a forced draught air-cooled heat exchanger. Since inclination increases plenum depth, the effect of inclination is also compared with increasing plenum depth without inclination. The experimental study shows that inclination improves thermal performance by only 0.5%, when compared with a baseline non-inclined case with a shallow plenum. Similarly, increasing plenum depth without inclination has a thermal performance benefit of approximately 1%. The numerical study shows that, as the heat exchanger is inclined, the low velocity core at the centre of the heat exchanger moves to one side.
Keywords
INCLINATION , Forced-draught air-cooled heat exchanger
Journal title
Applied Thermal Engineering
Serial Year
2013
Journal title
Applied Thermal Engineering
Record number
1905754
Link To Document