Title of article :
Optimization of X-shaped louvered fin and tube heat exchangers while maintaining the physical meaning of the performance evaluation criterion
Author/Authors :
Ameel، نويسنده , , Bernd and Degroote، نويسنده , , Joris and TʹJoen، نويسنده , , Christophe and De Jaeger، نويسنده , , Peter and Huisseune، نويسنده , , Henk and De Schampheleire، نويسنده , , Sven and Vierendeels، نويسنده , , Jan and De Paepe، نويسنده , , Michel، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Abstract :
The optimization of heat exchangers requires a goal function. A very common choice for this goal function is a performance evaluation criterion (PEC). However, most commonly used PECs are not only a function of the heat exchanger geometry, but also of the Reynolds number. For such optimizations, the Reynolds number should not be kept fixed as shown in this paper. Furthermore, the current work demonstrates how to account for the influence of the Reynolds number correctly, to maintain the physical meaning of the PEC. This method is applied to the optimization of the X-shaped louvered fin and round tube heat exchanger. The variable geometry VG-1 criterion is used as the PEC. A surrogate model is used to enhance the performance of the optimization routine.
Keywords :
CFD , Compact heat exchangers , PEC , Louvered , optimization , Performance evaluation criterion
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering