Title of article :
Numerical simulation of water spray for pre-cooling of inlet air in natural draft dry cooling towers
Author/Authors :
Alkhedhair، نويسنده , , Abdullah and Gurgenci، نويسنده , , Hal and Jahn، نويسنده , , Ingo and Guan، نويسنده , , Zhiqiang and He، نويسنده , , Suoying، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
9
From page :
416
To page :
424
Abstract :
This paper presents a numerical investigation of inlet air pre-cooling with water sprays to enhance the performance in Natural Draft Dry Cooling Towers (NDDCT). A 3-D numerical model of a test channel was generated and the evaporation from a single spray nozzle was analyzed. The droplet evaporation and the resulting cooling of air were predicted for a range of inlet air conditions and spray characteristics. The results showed that up to 81% evaporation can be achieved for water droplets of 20 μm at a velocity of 1 m/s and that, droplet transport and evaporation strongly depend on droplet size and air velocity.
Keywords :
Spray cooling , Natural draft , Complete evaporation , Numerical modelling , Pre-cooling
Journal title :
Applied Thermal Engineering
Serial Year :
2013
Journal title :
Applied Thermal Engineering
Record number :
1906304