Title of article :
New positions for an internal heat exchanger in a CO2 supercritical refrigeration plant. Experimental analysis and energetic evaluation
Author/Authors :
Sلnchez، نويسنده , , Daniel and Patiٌo، نويسنده , , Jorge and Llopis، نويسنده , , Rodrigo and Cabello، نويسنده , , Ramَn and Torrella، نويسنده , , Enrique and Fuentes، نويسنده , , Fernando Vicente، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2014
Pages :
11
From page :
129
To page :
139
Abstract :
IHX is probably, one of the most commonly alternative used to improve cooling capacity and COP in a CO2 refrigerating plant working in supercritical conditions. The “classical” position at gas-cooler exit has been analyzed by several authors with positive results. The aim of this work is to compare, from experimental approach, the energetic behavior of a refrigerating plant working with several IHX configurations: gas-cooler exit (classical position), liquid receiver exit, and in both positions at the same time. The energetic behavior includes: cooling capacity, power consumption and COP. Moreover, the discharge temperature reached on each position has been analyzed. he experimental results, a general improvement in COP and cooling capacity has been observed regardless the position of the IHX. A maximum increment of 13% on COP has been registered working with two IHX at the same time.
Keywords :
IHX , CO2 , Refrigeration plant , supercritical , COP
Journal title :
Applied Thermal Engineering
Serial Year :
2014
Journal title :
Applied Thermal Engineering
Record number :
1906629
Link To Document :
بازگشت