Title of article
Investigation of energy-efficient strategy for direct expansion air-cooled air conditioning systems
Author/Authors
Vakiloroaya، نويسنده , , Vahid and Samali، نويسنده , , Bijan and Pishghadam، نويسنده , , Kambiz، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2014
Pages
10
From page
84
To page
93
Abstract
This paper addresses the energy saving significance of air-cooled direct expansion (DX) air conditioning systems using liquid pressure amplification (LPA) technology along with proposed theoretical–empirical models for the system components. This method utilizes a refrigerant pump in the liquid line to allow the system operation at lower condensing pressure. An actual DX rooftop package is used for data collection. The performance of the proposed method is simulated using transient simulation software. Simulation tool was validated by comparing predicted and measured power consumption of the rooftop package. Results show that up to 42% power savings can be obtained using this approach.
Keywords
ENERGY SAVING , MODELING , Liquid pressure amplification , HVAC , Experimental study
Journal title
Applied Thermal Engineering
Serial Year
2014
Journal title
Applied Thermal Engineering
Record number
1907033
Link To Document