Title of article :
Influence of ambient conditions and water flow on the performance of pre-cooled natural draft dry cooling towers
Author/Authors :
He، نويسنده , , Suoying and Guan، نويسنده , , Zhiqiang and Gurgenci، نويسنده , , Hal and Jahn، نويسنده , , Ingo and Lu، نويسنده , , Yuanshen and M. Alkhedhair، نويسنده , , Abdullah، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2014
Abstract :
A simplified heat and mass transfer model in cellulose medium was developed to predict the air outlet temperature and humidity after evaporative cooling. The model was used to simulate the operation of pre-cooled Natural Draft Dry Cooling Towers (NDDCTs) by a validated MATLAB code. The effects of supplied water flow rate to the media, ambient temperature and humidity on the performance of pre-cooled NDDCTs were investigated. It was found that the effect of the selected water flow rates on tower performance is negligible. Both ambient temperature and humidity affect the tower performance.
Keywords :
Cellulose medium , Natural Draft Dry Cooling Tower , Heat rejection , Pressure drop
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering