Title of article :
Use of Bio-Amp, a commercial bio-additive for the treatment of grease trap wastewater containing fat, oil, and grease
Author/Authors :
Tang، نويسنده , , Hao L. and Xie، نويسنده , , Yuefeng F. and Chen، نويسنده , , Yen-Chih، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2012
Pages :
7
From page :
52
To page :
58
Abstract :
This research investigated the application of Bio-Amp, a commercial bio-additive for the treatment of fat, oil, and grease (FOG) in a grease trap, and evaluated potential impacts of treated effluent on downstream collection system and treatment processes. Results show that after Bio-Amp treatment, FOG deposit formation was reduced by 40%, implicating a potential reduction of sewer line blockages. Chemical oxygen demand (COD), total nitrogen (TN), total phosphorus (TP) and total fatty acids were reduced by 39%, 33%, 56%, and 59%, respectively, which represents an overall loading reduction of 9% COD, 5% TN and 40% TP received by the treatment plant from all the dining halls. On the other hand, readily biodegradable COD fractions significantly increased, which implies a potential improvement on Bio-P removal. Overall, the results showed that application of Bio-Amp in grease trap provides potential reduction of sewer line blockages, and can also alleviate downstream treatment burden.
Keywords :
Wastewater , Bio-additive , fog , FOG deposit , Bio-Amp
Journal title :
Bioresource Technology
Serial Year :
2012
Journal title :
Bioresource Technology
Record number :
1930264