Reddy، S. Radha Krishna نويسنده , , M، Trishulapani. نويسنده Holy Mary institute of Technology &Science, keesara, RR district, Hyderabad, AP , , SOMASANKARAPPA، C. نويسنده Holy Mary institute of Technology &Science, keesara, RR district, Hyderabad, AP , , SUBRAHMANYAM، JBV نويسنده Bharat Institute of Engineering & Technology, Mangalpally, Ibrahimpatnam, RR District, Hyderabad, AP ,
Issue Information :
روزنامه با شماره پیاپی 5 سال 2012
Pages :
6
From page :
390
To page :
395
Abstract :
Abstract — The application of a dynamic voltage restorer (DVR) connected to a wind-turbine-driven doubly fed induction generator (DFIG) is investigated. The setup allows the wind turbine system an uninterruptible fault ridethrough of voltage dips. The DVR can compensate the faulty line voltage, while the DFIG wind turbine can continue its nominal operation as demanded in actual grid codes. Simulation results for a 2 MW wind turbine and measurement results on a 22 kW laboratory setup are presented, especially for asymmetrical grid faults. They show the effectiveness of the DVR in comparison to the low-voltage ride-through of the DFIG using a crowbar that does not allow continuous reactive power production