Title of article :
Water-cooled electronics
Author/Authors :
Dumont، نويسنده , , G. and Fontaine Vive Roux، نويسنده , , Ph. and Righini، نويسنده , , B.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
11
From page :
213
To page :
223
Abstract :
LHC experiments demand on cooling of electronic instrumentation will be extremely high. A large number of racks will be located in underground caverns and counting rooms, where cooling by conventional climatisation would be prohibitively expensive. A series of tests on the direct water cooling of VMEbus units and of their standard power supplies is reported. A maximum dissipation of 60 W for each module and more than 1000 W delivered by the power supply to the crate have been reached. These values comply with the VMEbus specifications.
Keywords :
LHC , COOLING , water cooling , Power-supply , VMEbus
Journal title :
Nuclear Instruments and Methods in Physics Research Section A
Serial Year :
2000
Journal title :
Nuclear Instruments and Methods in Physics Research Section A
Record number :
2184542
Link To Document :
بازگشت