• Title of article

    Two-dimensional modelling of the ice accretion process on transmission line wires and conductors

  • Author/Authors

    Fu، نويسنده , , Ping and Farzaneh، نويسنده , , Masoud and Bouchard، نويسنده , , Gilles، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2006
  • Pages
    15
  • From page
    132
  • To page
    146
  • Abstract
    The main objective of this paper is to introduce a new 2-D icing model, of which the primary purpose is the simulation of the ice accretion process on overhead power line cables. The parameters of the model, such as the Local Collision Efficiency (LCE) and the local Heat Transfer Coefficient (HTC), were evaluated on the basis of time-dependent airflow computations and water droplet trajectory calculations. For wet accumulations, the movement of a surface water film was monitored at each time step so as to obtain the filmʹs thickness and direction. In order to validate the present model, a number of experimental tests were carried out at the CIGELE Atmospheric Icing Research Wind Tunnel (CAIRWT). The results show that, on the whole, the proposed ice model performed well in simulating and predicting ice-grown shapes under dry and wet icing conditions.
  • Keywords
    Airflow computation , Fluid boundary layer , Surface water flow , ice accretion , Computer simulation
  • Journal title
    Cold Regions Science and Technology
  • Serial Year
    2006
  • Journal title
    Cold Regions Science and Technology
  • Record number

    2271506