Title of article
Effects of inlet relative humidity and inlet temperature on the performance of counterflow wet cooling tower based on exergy analysis
Author/Authors
Muangnoi، نويسنده , , Thirapong and Asvapoositkul، نويسنده , , Wanchai and Wongwises، نويسنده , , Somchai، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
6
From page
2795
To page
2800
Abstract
The purpose of this study is to analyze the influence of the ambient temperature and humidity on the performance of a counterflow wet cooling tower according to the second law, exergy analysis, of thermodynamics. First, the properties of water and air flow through the tower were predicted and validated by the experiment. Exergy analysis then has been carried out for investigating the cooling tower performance with various inlet air conditions, relative humidity and dry bulb temperature, while the water side condition is kept constant. According to the analysis in this paper, the similar result in terms of required dry air flow rate, exergy change of water and that of air, exergy destruction and second law efficiency were obtained for the various inlet air conditions. The exergy change of water Δxw is higher than that of air Δxair, since Δxw is the available energy of water to supply to air throughout the tower while Δxair is the available energy of air to recover or utilize that supplied by water. It reveals that Δxair is dominated by the exergy change of air due to evaporative heat transfer. In addition, it gives a clearer explanation of the cooling tower performance and gives clear trends for optimization.
Keywords
Wet cooling tower , Second law efficiency , Exergy analysis , Exergy change
Journal title
Energy Conversion and Management
Serial Year
2008
Journal title
Energy Conversion and Management
Record number
2334180
Link To Document