Title of article :
Heat pipe for cooling of electronic equipment
Author/Authors :
Chang، نويسنده , , Yu-Wei and Cheng، نويسنده , , Chiao-Hung and Wang، نويسنده , , Jung-Chang and Chen، نويسنده , , Sih-Li Chen، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Abstract :
This article experimentally investigates the thermal performance of the heat pipe cooling system with the thermal resistance model. Evaporator and condenser, which are the two main devices, connect to each other to form a closed system. The liquid water absorbs heat from heat source and evaporates in the evaporator. The evaporating fluid moves toward the condenser, and then condenses in the condenser. The experimental parameters are different evaporation surfaces, fill ratios of working fluid and input heating powers. The result shows that the evaporation resistance and the condensation resistance both grow with increasing heating power and decreasing fill ratio. Flooding is found at the fill ratio of 20% with the evaporation surface noted Etched Surface 2 when heating power is above 120 W. Flooding phenomenon is caused by the opposite flow direction of vapor and liquid in a closed two-phase system. According to the result, the lowest total thermal resistance is 0.65 °C/W by the evaporation surface noted Etched Surface 2 at 30% fill ratio.
Keywords :
heat pipe , Flooding phenomenon , Thermal Performance , Thermal Resistance
Journal title :
Energy Conversion and Management
Journal title :
Energy Conversion and Management