• Title of article

    Performance enhancement of a subcooled cold storage air conditioning system

  • Author/Authors

    Hsiao، نويسنده , , Ming-Jer and Cheng، نويسنده , , Chiao-Hung and Huang، نويسنده , , Ming-Chao and Chen، نويسنده , , Sih-Li Chen، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    7
  • From page
    2992
  • To page
    2998
  • Abstract
    This article experimentally investigates the enhancement of thermal performance for an air conditioning system utilizing a cold storage unit as a subcooler. The cold storage unit is composed of an energy storage tank, liquid-side heat exchanger, suction-side heat exchanger and energy storage material (ESM), water. When the cooling load is lower than the nominal cooling capacity of the system, the cold storage unit can store extra cold energy of the system to subcool the condenser outlet refrigerant. Hence, both the cooling capacity and coefficient of performance (COP) of the system will be increased. This experiment tests the two operation modes: subcooled mode with energy storage and non-subcooled mode without energy storage. The results show that for fixed cooling loads at 3.05 kW, 3.5 kW and 3.95 kW, the COP of the subcooled mode are 16.0%, 15.6% and 14.1% higher than those of the non-subcooled mode, respectively. In the varied cooling load experiments, the COP of the subcooled cold storage air conditioning system is 15.3% higher than the conventional system.
  • Keywords
    Subcooled , Cold storage unit , Energy storage material
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2009
  • Journal title
    Energy Conversion and Management
  • Record number

    2334939