Title of article :
Thermal analysis of cast-resin dry-type transformers
Author/Authors :
Eslamian، نويسنده , , M. and Vahidi، نويسنده , , B. and Eslamian، نويسنده , , A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Abstract :
Non-flammable characteristic of dry-type cast-resin transformers make them suitable for residential and hospital usages. However, because of resin’s property, thermal behavior of these transformers is undesirable, so it is important to analyze their thermal behavior. In this paper temperature distribution of cast-resin transformers is modeled by two different approaches. A FEM-based model which uses experimental-analytical formula for air–cooling vertical ducts and a 3D finite volume based CFD model which is established in the ANSYS CFX software. In order to evaluate and compare the models, the simulation results were compared with the experimental data measured from an 800 kVA transformer. Finally, the influences of some construction parameters and environmental conditions on temperature distribution of cast-resin transformers were discussed.
Keywords :
CFD , Cast-resin dry-type transformer , Thermal modeling , FEM
Journal title :
Energy Conversion and Management
Journal title :
Energy Conversion and Management