Title of article :
Analytical calculation of detailed model parameters of cast resin dry-type transformers
Author/Authors :
Eslamian، نويسنده , , M. and Vahidi، نويسنده , , B. and Hosseinian، نويسنده , , S.H.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
10
From page :
2565
To page :
2574
Abstract :
Non-flammable characteristic of cast resin dry-type transformers make them suitable for different kind of usages. This paper presents an analytical method of how to obtain parameters of detailed model of these transformers. The calculated parameters are compared and verified with the corresponding FEM results and if it was necessary, correction factors are introduced for modification of the analytical solutions. Transient voltages under full and chopped test impulses are calculated using the obtained detailed model. In order to validate the model, a setup was constructed for testing on high-voltage winding of cast resin dry-type transformer. The simulation results were compared with the experimental data measured from FRA and impulse tests.
Keywords :
Cast resin dry-type transformer , Parameter calculation , Detailed model , Impulse test , FEM , FRA
Journal title :
Energy Conversion and Management
Serial Year :
2011
Journal title :
Energy Conversion and Management
Record number :
2335681
Link To Document :
بازگشت