Title of article :
Experimental investigation of a pilot compression chiller with alternatives refrigerants using compact heat exchanger
Author/Authors :
Hassan، نويسنده , , M.A.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
8
From page :
277
To page :
284
Abstract :
This paper reports the results of an experimental investigation on a pilot compression chiller working with R407C and R410A as R22 alternatives using compact heat exchanger. Experiments are conducted and the influences of the cooling water mass flow rate (200–2500 kg/h), cooling water inlet temperature (20–45 °C) and chilled water mass flow rate (200–1500 kg/h) on performance characteristics of chillers are evaluated for R22, R407C and R410A. sing the cooling water mass flow rate or decreasing its inlet temperature causes the operating pressures and electric input power to decrease while the cooling capacity and coefficient of performance (COP) increase. The pressure ratio is reduced while actual loads and COP are increased with the chilled water mass flow rate. The effect of cooling water inlet temperature on the system performance is more significant than the effects of cooling and chilled water mass flow rates. Comparison between R22, R407C and R410A under identical operating conditions has been done. An enhancement is obtained when using compact heat exchanger than shell and tube heat exchanger, this enhancement is about 8.5% in the coefficient of performance.
Keywords :
R407C , Water cooled chillers , R410A , Performance
Journal title :
Energy Conversion and Management
Serial Year :
2013
Journal title :
Energy Conversion and Management
Record number :
2336570
Link To Document :
بازگشت