Title of article :
The application of a desiccant wheel to increase the energetic performances of a transcritical cycle
Author/Authors :
Aprea، نويسنده , , Ciro and Greco، نويسنده , , Adriana and Maiorino، نويسنده , , Angelo، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2015
Pages :
9
From page :
222
To page :
230
Abstract :
A desiccant dehumidification system with air can be driven by low grade (<80 °C) waste heat. In this paper, which is based on experimental data, the air flow at the outlet of the gas cooler of a trans-critical cycle is forced through a desiccant wheel regenerated by the air flow itself. The hybrid trans-critical refrigerator-desiccant system improves COP by approximately 77% as compared to a classical transcritical. The economical analysis suggests that the investment return-time is acceptable (lower than about 8 years) only at ambient temperature exceeding 35 °C. The ecological analysis indicates that the TEWI of the classical transcritical cycle exceeds that of the hybrid system, by approximately 60%.
Keywords :
Hybrid System , Simple Pay Back Period , Desiccant wheel , Trans-critical cycle , TEWI , Discount Pay Back Period , CO2 , Coefficient of Performance
Journal title :
Energy Conversion and Management
Serial Year :
2015
Journal title :
Energy Conversion and Management
Record number :
2338781
Link To Document :
بازگشت