Title of article :
Failure analysis of perforation in salty water-wall tubes of a power plant
Author/Authors :
Dorri، نويسنده , , Mohammad and Harandizadeh، نويسنده , , Davoud، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2012
Pages :
10
From page :
87
To page :
96
Abstract :
Perforation of water-wall of saline panels in Shahid-Montazeri power plant led to some systematic serious problems. XRD and XRF investigation along with spectrometric and metallographic analysis proved that perforation is mainly due to caustic corrosion. Moreover; it was concluded that significant amount of copper ions entered into the water circulation line and caused higher corrosion rate. It’s evident that variation in oxygen concentration and base metal decarburization were also effective in corrosion deterioration. Reduction in water-wall over-deposition and regular descaling along with modification of heating rate and replacing lithium hydroxide and ammonia with suitable modifiers, helped to overcome the problem.
Keywords :
Corrosion , Power plant , Failure mechanism , Boiler tube , Boiler Failure
Journal title :
Engineering Failure Analysis
Serial Year :
2012
Journal title :
Engineering Failure Analysis
Record number :
2339466
Link To Document :
بازگشت