• Title of article

    Failure analysis of perforation in salty water-wall tubes of a power plant

  • Author/Authors

    Dorri، نويسنده , , Mohammad and Harandizadeh، نويسنده , , Davoud، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    10
  • From page
    87
  • To page
    96
  • Abstract
    Perforation of water-wall of saline panels in Shahid-Montazeri power plant led to some systematic serious problems. XRD and XRF investigation along with spectrometric and metallographic analysis proved that perforation is mainly due to caustic corrosion. Moreover; it was concluded that significant amount of copper ions entered into the water circulation line and caused higher corrosion rate. It’s evident that variation in oxygen concentration and base metal decarburization were also effective in corrosion deterioration. Reduction in water-wall over-deposition and regular descaling along with modification of heating rate and replacing lithium hydroxide and ammonia with suitable modifiers, helped to overcome the problem.
  • Keywords
    Corrosion , Power plant , Failure mechanism , Boiler tube , Boiler Failure