Title of article :
Effect of coking in massive failure of tubes in an ethylene cracking furnace
Author/Authors :
Otegui، نويسنده , , Jose Luis and Bona، نويسنده , , Jeremيas De and Fazzini، نويسنده , , Pablo G.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2015
Abstract :
The causes and characteristics of the massive failure of the radiant coil tubes in an ethylene cracking furnace, which failed during an emergency non-programmed stop, are investigated. The failed tubes had been in service for about three and a half years, while lifetime had been estimated in five years. Tensile testing showed severe in-service degradation of material mechanical properties. Longitudinal cracks on failed tubes are brittle and originate in the inner side of the tubes wall. All failed tubes display a thick layer of coke adhered to the inner wall. This coke comes easily broken by bending or tension stresses, but sustains compression.
igins of loads which lead to the fracture were replicated; cracks were lab-induced by longitudinal cutting and resulting openings measured. Mechanical modeling allowed concluding that loads that led to failures were due to differences between thermal expansion coefficients of tube alloy and the coke growth within them. When the furnace was cooled down, thermal contraction of tube metal was restricted by the thick coke layer. This layer grew in service in the pressure expanded tubes.
ilures were due to a combination of circumferential loads induced by coke during fast cooling and low strength of tube material. Recommendations include monitoring coke thickness and comparing with critical thickness for tube rupture in case of an emergency stop. This way, operators will have a parameter useful to schedule decoke processes.
Keywords :
Ethylene furnace , Coke thickness , Tube cracking , Emergency stop
Journal title :
Engineering Failure Analysis