Abstract :
This paper deals with the requirements, operational modes and design of the cooling system for the ITER Neutral Beam test experiments. Different operating conditions of the experiments have been considered in order to identify the maximum heat loads that constitute, with the inlet temperature and pressure at each component, the design requirements for the cooling system. st facility components will be actively cooled by ultrapure water realizing a closed cooling loop for each group of components. Electrochemical corrosion issues have been taken into account for the design of the primary cooling loops and of the chemical and volume control system that will produce water with controlled resistivity and pH. Draining and drying systems have been designed to evacuate water from the components and primary loops in case of leakage, and to carry out leak detection. m concentration, water resistivity and pH will be measured and monitored at each primary loop for safety reasons and high voltage holding reliability. The measured water flow rates and temperatures will be used to calculate the exchanged heat fluxes and powers. Flow regulating valves and speed of variable driven pumps will be adjusted to control the component temperatures in order to fulfil the functional and thermohydraulic requirements.
Keywords :
Cooling System , ITER , Neutral Beam Injectors , Heat transfer systems , Drying system
Journal title :
Fusion Engineering and Design
Serial Year :
2009
Journal title :
Fusion Engineering and Design
Record number :
2356014
Link To Document :
بازگشت