Abstract :
The paper presents the results of development and testing of an explosively actuated circuit-breaker (the so-called pyrobreaker) designed and manufactured at the Efremov Institute [1]. In accordance with the ITER specifications this switch will be used for continuous operation with DC currents up to 70 kA and shall be capable, on command, to transfer this current to a resistive load under a voltage up to 10 kV in less than 1 ms. er of current commutation tests have been carried out on several prototypes [2]. The last experimental campaign has demonstrated reliable operation of the pyrobreaker with 20% safety margin for the interrupted current and 100% margin for the recovery voltage relative to the ITER requirements. s, peak current withstand tests have been performed with pulse currents up to 420 kA generated by the unipolar current generator available at the Efremov Institute.
Keywords :
Pyrobreaker , DC circuit breaker , Energy discharge , quench protection , Explosively actuated switch