Title of article
Stabilization of power system for large-scaled experimental fusion facility
Author/Authors
Yamada، نويسنده , , S and Kitagawa، نويسنده , , S and Chikaraishi، نويسنده , , H and Murai، نويسنده , , K and Mizuno، نويسنده , , Y and Saito، نويسنده , , F and Hayakawa، نويسنده , , A and Sawamura، نويسنده , , H and Ise، نويسنده , , T and Sato، نويسنده , , Y and Kaneko، نويسنده , , O and Nakamura، نويسنده , , Y and Satow، نويسنده , , T and Motojima، نويسنده , , O، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
5
From page
35
To page
39
Abstract
In the early experiments of the LHD, the harmful third harmonic currents had been observed in the power line of the NIFS substation, when the fly-wheel motor generator (MG) for the neutral beam injection (NBI) reaccelerates between the plasma productions. The variable harmonic currents, which were estimated to be 1±6 and 1±12 ns, were induced through a Scherbius device. They extremely resonated to the circuit impedance of the power line. To stabilize electrical power in the site, following modifications were conducted: (1) reduction of the harmonic current from the Scherbius device; (2) reconnection of the power supplies of the SC coils and heating devices to suitable power feeders; (3) compensation of lagging reactive power of the MG. As a result, harmful harmonic currents were suppressed.
Keywords
High-Pass Filter , LHD , Harmonic currents , Scherbius device
Journal title
Fusion Engineering and Design
Serial Year
2001
Journal title
Fusion Engineering and Design
Record number
2367100
Link To Document