Title of article :
Effective pipe-to-borehole thermal resistance for vertical ground heat exchangers
Author/Authors :
Sharqawy، نويسنده , , Mostafa H. and Mokheimer، نويسنده , , Esmail M. and Badr، نويسنده , , Hassan M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Abstract :
The effective pipe-to-borehole thermal resistance of a vertical ground heat exchanger is investigated numerically. An analysis is carried out to determine the dimensionless geometrical parameters affecting such resistance. The heat transfer rates between the U-shaped pipes and the borehole are determined numerically and compared with some well-known limiting analytical solutions. A best-fit correlation for the effective pipe-to-borehole thermal resistance is presented in dimensionless form. The results are compared against approximate analytical solutions that represent the U-shaped pipes as a single pipe of equivalent diameter and against experimental data available in the literature. It is found that the available models do not accurately represent the effective pipe-to-borehole thermal resistance.
Keywords :
Ground coupled heat pump , ground heat exchanger , borehole , Thermal Resistance , Geothermal
Journal title :
Geothermics
Journal title :
Geothermics