Title of article :
Sensor fault detection and isolation via high-gain observers: Application to a double-pipe heat exchanger
Author/Authors :
Escobar، نويسنده , , R.F. and Astorga-Zaragoza، نويسنده , , C.M. and Téllez-Anguiano، نويسنده , , A.C. and Juلrez-Romero، نويسنده , , D. and Hernلndez، نويسنده , , J.A. and Guerrero-Ramيrez، نويسنده , , G.V.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
7
From page :
480
To page :
486
Abstract :
This paper deals with fault detection and isolation (FDI) in sensors applied to a concentric-pipe counter-flow heat exchanger. The proposed FDI is based on the analytical redundancy implementing nonlinear high-gain observers which are used to generate residuals when a sensor fault is presented (as software sensors). By evaluating the generated residual, it is possible to switch between the sensor and the observer when a failure is detected. Experiments in a heat exchanger pilot validate the effectiveness of the approach. The FDI technique is easy to implement allowing the industries to have an excellent alternative tool to keep their heat transfer process under supervision. The main contribution of this work is based on a dynamic model with heat transfer coefficients which depend on temperature and flow used to estimate the output temperatures of a heat exchanger. This model provides a satisfactory approximation of the states of the heat exchanger in order to allow its implementation in a FDI system used to perform supervision tasks.
Keywords :
FDI , High-gain observers , Heat exchangers
Journal title :
ISA TRANSACTIONS
Serial Year :
2011
Journal title :
ISA TRANSACTIONS
Record number :
2383117
Link To Document :
بازگشت