Title of article :
Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems
Author/Authors :
Amanifard، F نويسنده , , Ramezani، N نويسنده ,
Issue Information :
فصلنامه با شماره پیاپی سال 2016
Abstract :
Abstract: The article presents the transients analysis of the substation grounding systems
and transmission line tower footing resistances which can affect to the back-flashover (BF)
or overvoltage across insulator chain in an HV power systems by using EMTP-RV
software. The related transient modeling of the grounding systems is based on a
transmission line (TL) model with considering the soil ionization. In addition, different
configuration of grounding system have been simulated to calculated the BF, including
number of vertical grounding rod, length of rod, point of lightning current injection into the
grounding grid and using two depth design of grounding system where the surface of
substation under consideration is very small orit is necessary to bury the grounding grid in
the rocky media, occasionally. The simulation results have shown that how the mentioned
parameters can considerably affect inception of BF, and suitable design of grounding
system can reduce damages caused by lightning.
Keywords :
Grounding System , Transient modeling , Back-flashover (BF)
Journal title :
Iranian Journal of Electrical and Electronic Engineering(IJEEE)
Journal title :
Iranian Journal of Electrical and Electronic Engineering(IJEEE)