Title of article :
Simultaneous power sharing and protection against faults for DGs in microgrid with different loads
Author/Authors :
Rajamand, Sahbasadat Department of electrical engineering - Songhor Branch - Islamic Azad university, Songhor , ketabi, Abbas Department of electrical engineering - Kashan university, Kashan , Zahedi, Abdulhamid Department of electrical engineering - Kermanshah university of technology, Kermanshah
Abstract :
The LVRT (Low Voltage Ride Through) is the main characteristic
of every power system in faulty conditions. When fault occurs, it
is essential for power system such as microgrid to control the
voltage and frequency normally. Naturally in fault status, the
unbalanced voltage and current are inevitable, but with the aid
of LVRT technique, microgrid can keep stability in main system
parameters such as voltage and current of each phase. In this
paper, the microgrid is proposed in islanded state and using the
reactive power injection in faulty conditions, and the LVRT
technique is applied. When reactive power is inserted,
simultaneously the active power must be reduced, and so the
current is limited, and overcurrent is controlled. Simulation
results indicate that this strategy enhances the presentation of
the structure in symmetric and asymmetric faults. That is
noticeable declaring that the suggested approach has not
degraded the power sharing among DGs both in faulty and
faultless status and also plug and play property is kept using this
suggested LVRT strategy.
Keywords :
Protection Method , Faulty Conditions , Symmetric Fault , Asymmetric Fault , Power Sharing
Journal title :
Astroparticle Physics