Title of article :
Discrimination of Inrush from Fault Currents in Power Transformers Based on Equivalent Instantaneous Inductance Technique Coupled with Finite Element Method
Author/Authors :
Jamali, M. babol noshirvani university of technology - Department of Electrical and ComputerEngineering, بابل, ايران , Mirzaie, M. babol noshirvani university of technology - Department of Electrical and Computer Engineering, بابل, ايران , Gholamian, S. A. babol noshirvani university of technology - Department of Electrical and Computer Engineering, بابل, ايران
From page :
197
To page :
202
Abstract :
The phenomenon of magnetizing inrush is a transient condition, which occurs primarily, when a transformer is energized. The magnitude of inrush current may be as high as ten times or more times of transformer rated current that causes malfunction of protection system. So, for safe running of a transformer, it is necessary to distinguish inrush current from fault currents. In this paper, an equivalent instantaneous inductance (EII) technique is used to discriminate inrush current from fault currents. For this purpose, a three-phase power transformer has been simulated in Maxwell software that is based on finite elements. This three-phase power transformer has been used to simulate different conditions. Then, the results have been used as inputs in MATLAB program to implement the equivalent instantaneous inductance technique. The results show that in the case of inrush current, the equivalent instantaneous inductance has a drastic variation, while it is almost constant in the cases of fault conditions.
Keywords :
Equivalent Instantaneous Inductance , Finite Element , Inrush Current
Journal title :
Iranian Journal of Electrical and Electronic Engineering(IJEEE)
Journal title :
Iranian Journal of Electrical and Electronic Engineering(IJEEE)
Record number :
2551314
Link To Document :
بازگشت