• Title of article

    AN EXPERIMENTAL STUDY ON SUBCOOLING PROCESS OF A TRANSCRITICAL CO2 AIR CONDITIONING CYCLE WORKING WITH MICROCHANNEL EVAPORATOR

  • Author/Authors

    Dang, T. Department of Thermal Engineering - HCMC University of Technology and Education, Vietnam , Vo, K. Department of Thermal Engineering - HCMC University of Technology and Education, Vietnam , Le, C. Department of Heat and Refrigeration Engineering - HCMC University of Technology – VietnamNational University, Ho Chi Minh City, Vietnam , Nguyen, T. Department of Thermal Engineering - HCMC University of Technology and Education, Vietnam

  • Pages
    10
  • From page
    1505
  • To page
    1514
  • Abstract
    An experimental study on subcooling process of a transcritical CO2 air conditioning cycle working with microchannel evaporator was done. In this cycle there are two different subcoolers namely S1 and S2 were installed and tested. The experimental data show that the COP of the cycle working with the subcooler S2 is better which is at 7.2. The evaporator pressure, the subcooler pressure, the subcooling temperature and the compressor current corresponding to the above-mentioned COP are 44 bar, 75 bar, 26 ºC, and 2.4 A, respectively. A total comparison between the present study and other literatures was also indicated which confirms that the results gained by the present study look better.
  • Keywords
    CO2 refrigerant , Air conditioning system , Subcooling , Heat transfer , Microchannel
  • Journal title
    Journal of Thermal Engineering
  • Serial Year
    2017
  • Record number