Title of article :
A SIMULATED STUDY ON THE EFFECT OF WATER TEMPERATURE ON COOLING EFFICIENCY OF WATER MIST FIRE EXTINGUISHERS
Author/Authors :
Omidvar, Amir Department of Mechanical Engineering - Shiraz University of Technology, Shiraz , Mahdavi, Amirhossein Department of Mechanical Engineering - University of Alberta, Edmonton,Canada , Mehryar, Reza Department of Mechanical Engineering - Shiraz University of Technology, Shiraz
Pages :
14
From page :
460
To page :
473
Abstract :
In this paper, the effect of initial water temperature on the cooling performance of a water mist fire suppression system has been investigated. A zero-dimensional analytical model was first developed to study the thermal and dynamic behavior of a single water droplet. The developed model was validated against available experimental data in the literature. The developed model was further extended to simulate the transient heating, evaporation, break-up, and liquid penetration length of a hollow-cone water spray. Results indicated that increasing the initial temperature of the water spray before injection resulted in a decrease in the initial size distribution of the spray droplets. It was further found that the evaporation time of the injected droplets decreased by about 11% and the cooling power of the preheated water mist system enhanced by 12% in exchange for increasing the initial temperature of the water spray by 10˚C. It was concluded that pre-heating the sprayed water droplets would likely improve the cooling efficiency of the water mist system. It could be also inferred that at equal cooling power, less water was consumed by the pre-heated spray compared to conventional water mist systems.
Keywords :
Cooling Efficiency , Droplet Evaporation , Spray Formation , Water Mist System
Journal title :
Journal of Thermal Engineering
Serial Year :
2020
Full Text URL :
Record number :
2594228
Link To Document :
بازگشت