Title of article :
COMPUTATION OF THE SPLIT FACTOR OF EARTH FAULT CURRENTS BY CONSIDERING THE PROXIMITY EFFECTS
Author/Authors :
RAMEZANI, N. University of Science and Technology (lUST),Behshahr Branch, ايران , SHAHRTASH, S.M. iran university of science and technology - Center of Excellence for Power System Automation and Operation - Dept of Electrical Engineering, تهران, ايران
From page :
289
To page :
305
Abstract :
To determine a safe substation grounding grid in power systems, it is important tocompute the split factor for earth fault current including the proximity influences among the gridand the earthing systems of the incoming/outgoing transmission lines towers. In this paper, anovel, simple and accurate method is developed for computing this factor that can correctly takeinto account the proximity effects. The results are compared with those that have been published(for the cases that they are able to compute) which show good agreement and accuracy.
Keywords :
Split factor , proximity effects , earth fault currents , touch and step voltages , grounding grid design
Journal title :
Iranian Journal of Science and Technology :Transactions of Electrical Engineering
Journal title :
Iranian Journal of Science and Technology :Transactions of Electrical Engineering
Record number :
2596318
Link To Document :
بازگشت