Title of article :
Breakdown Voltage and Resistivity of MO and RBDPO mixture as potential Liquid Insulation at Ambient Temperature of Transformers
Author/Authors :
yusnida, m.y. universiti teknologi mara - faculty of electrical engineering, Shah Alam, Malaysia , abidin, ahmad farid universiti teknologi mara - advanced computing communication communities of research, electrical power engineering and power system of faculty of electrical engineering,, Shah Alam, Malaysia , mat yusoh, mohd abdul talib universiti teknologi mara - faculty of electrical engineering, Shah Alam, Malaysia
Abstract :
The paper presents an investigation based on an experimental work of the dielectric behavior for transformer oil with palm oil at different mixture and temperature. The basic properties of transformers mineral insulating oil should be introduced to have a better understanding of dielectric strength of oil mixture. The author has highlighted oil resistivity and breakdown voltage (BDV) during the experimental work of Deodorized Palm Oil (RBDPO) mixed with transformer oil namely mineral oil (MO) at 40°C to 60°C. Testing was made at 40°C to 60°C according to IEC 156 standard by using AC Modul System circuit of Hivolt Power Diagnostic and MegaOhm 1KV 3005A megger was used to evaluate the resistivity. The highest breakdown strength is achieved 44kv at 80% of RBDPO content. The result of resistivity that was influenced by temperature also presented.
Keywords :
Refined Bleached Deodorized Palm Oil , Mineral Oil , Insulation , Breakdown Voltage , Resistivity
Journal title :
International Journal Of Electrical and Electronic Systems Research
Journal title :