Title of article :
A STUDY OF ENERGY EFFICIENCY, ECONOMIC AND ENVIRONMENTAL BENEFITS OF A COOLING TOWER
Author/Authors :
Saidur, R. university of malaya - Department of Mechanical Engineering, Malaysia , Abdelaziz, E.A. Bangladesh University of Engineering and Technology (BUET) - Department of Mechanical Engineering, Bangladesh , Hasanuzzaman, M. Bangladesh Agricultural University - Department of agronomy, Bangladesh , Mamun, M.A.H. Saga University - Institute of Ocean Energy, Japan
From page :
87
To page :
94
Abstract :
Cooling tower is one of the most important utilities in industrial and residential facilities. This paper estimates the energy efficiency, economic and environmental benefits of cooling tower. Energy-saving measures by using the high efficient motors and variable speed drive (VSD) were applied to save energy. By installing VSD in the cooling tower’s fans, annual energy saving have been found to be 202,972 kWh and potential emissions reduction is about 120 ton of CO2, 661 kg of SO2, 312 kg of NOx and 661 kg of CO at different cooling load. By using high efficient motor, emissions reduction are about 6.97 ton of CO2, 38,400 kg of SO2, 18,109 kg of NOx and 4,601 kg of CO at 50 % load. A sizeable amount of utility bill can be saved by using high efficient motors and applying VSDs. Payback periods for different energy savings measures have been estimated and found to be economically viable
Keywords :
Energy , Efficiency , Cooling tower , Environment
Journal title :
International Journal of Mechanical and Materials Engineering
Journal title :
International Journal of Mechanical and Materials Engineering
Record number :
2663362