Title of article :
Increasing electricity generation per unit of fossil fuel so expended in diesel engines
Author/Authors :
Probert، D. نويسنده , , Dunstan، D. نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Pages :
-266
From page :
267
To page :
0
Abstract :
An evaporatorʹs time-constant (tc) equation has been developed as part of a mathematical model describing the time-dependent behaviour of a refrigeration system. The magnitudes of the evaporatorʹs tc were approximately 2 and 5 s, respectively for 100 and 50% loads imposed on the refrigerator. As a result of a step change in the inletʹs water-temperature, the magnitudes of both tc and the two-phase heat-transfer coefficient (ftp) for the refrigerant system were altered. Although a step decrease in the inlet-waterʹs temperature led to large increase in tc the systemʹs behaviour stabilized quickly because ftp had also increased significantly. The predictions of this investigation showed that such an analysis is highly sensitive to the accuracy of the equations used to calculate both tc and ftp and this makes the experimental verification of this model desirable.
Keywords :
Electric vehicle , Infrastructure , Air pollutant , Lite cycle analysis
Journal title :
Applied Energy
Serial Year :
2001
Journal title :
Applied Energy
Record number :
3313
Link To Document :
بازگشت