Title of article :
Moderately high temperature water source heat-pumps using a near-azeotropic refrigerant mixture
Author/Authors :
Shi، Lin نويسنده , , Nanxi، Liu نويسنده , , Lizhong، Han نويسنده , , Mingshan، Zhu نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
-434
From page :
435
To page :
0
Abstract :
A ternary mixture of R124/R142b/R600a, named HTR01, for moderately high temperature heat pumps, was developed. Tests of material compatibility and oil miscibility showed that the mixture could be used with a R22 compressor in an HTR01 heat-pump system. A 2.92 kW moderately high temperature water source heat pump system was set up with HTR01 as the refrigerant to study the system performance with HTR01. Then, a 300 kW moderately high temperature water source heat pump system was built with HTR01 as the refrigerant to test the performance with a geothermal hot water source. The test showed that the condenser outlet water temperature could reach and hold on about 90 °C with a high coefficient of performance.
Keywords :
Refrigerant mixtures , Heat pumps , Water source heat pump
Journal title :
Applied Energy
Serial Year :
2005
Journal title :
Applied Energy
Record number :
3515
Link To Document :
بازگشت