Thermal performance evaluation of an energy and environmental research center building during winter
Author/Authors
Al-Karaghouli، A. نويسنده , , Abood، I. نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2000
Pages
-230
From page
231
To page
0
Abstract
The building is constructed on a ground area of 3300 m^2 and consists of five floors of total area of 6361 m^2 with an air conditioned area of 3351 m^2. The heating system comprises 1577 evacuated-tube collectors, two accumulation tanks of 15 m^3 each, two thermal storage tanks of 150 m^ each, two auxiliary boilers of 443,000 kcal/h each, pumps, heat exchangers and control equipment. The thermal performance evaluation shows that the inside temperature was kept at the desired value (22°C) which demonstrates the systemʹs ability to meet the building load. The performance also shows that the collection efficiency for the whole season was 50% and the collected and stored energy was higher than the required load which indicates that the solar fraction to the load was 100%.
Keywords
Full chain-energy systems , health , environmental impact , Comparative assessment