• Title of article

    Thermal performance evaluation of an energy and environmental research center building during winter

  • Author/Authors

    Al-Karaghouli، A. نويسنده , , Abood، I. نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2000
  • Pages
    -230
  • From page
    231
  • To page
    0
  • Abstract
    The building is constructed on a ground area of 3300 m^2 and consists of five floors of total area of 6361 m^2 with an air conditioned area of 3351 m^2. The heating system comprises 1577 evacuated-tube collectors, two accumulation tanks of 15 m^3 each, two thermal storage tanks of 150 m^ each, two auxiliary boilers of 443,000 kcal/h each, pumps, heat exchangers and control equipment. The thermal performance evaluation shows that the inside temperature was kept at the desired value (22°C) which demonstrates the systemʹs ability to meet the building load. The performance also shows that the collection efficiency for the whole season was 50% and the collected and stored energy was higher than the required load which indicates that the solar fraction to the load was 100%.
  • Keywords
    Full chain-energy systems , health , environmental impact , Comparative assessment