Title of article :
Design and simulation of a new energyconscious system (CFD and solar simulation)
Author/Authors :
Gadi، Mohamed B. نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Pages :
-250
From page :
251
To page :
0
Abstract :
The building is constructed on a ground area of 3300 m^2 and consists of five floors of total area of 6361 m^2 with an air conditioned area of 3351 m^2. The heating system comprises 1577 evacuated-tube collectors, two accumulation tanks of 15 m^3 each, two thermal storage tanks of 150 m^ each, two auxiliary boilers of 443,000 kcal/h each, pumps, heat exchangers and control equipment. The thermal performance evaluation shows that the inside temperature was kept at the desired value (22°C) which demonstrates the systemʹs ability to meet the building load. The performance also shows that the collection efficiency for the whole season was 50% and the collected and stored energy was higher than the required load which indicates that the solar fraction to the load was 100%.
Keywords :
CFD , Solar simulator , Fluent , Water-heater