Author/Authors :
Kezunovic، نويسنده , , M.، نويسنده , , Xia، نويسنده , , Y.Q.، نويسنده , , Guo، نويسنده , , Y.، نويسنده , , Bastian Fromen، نويسنده , , C.W.، نويسنده , , Sevcik، نويسنده , , D.R.، نويسنده ,
Abstract :
This paper describes a test method for distance
relays using an advanced open-loop digital simulator.
Derivation of test signals during prefault and fault, and test
procedure are introduced. It is demonstrated that the method
of generating test signals and the procedure of applying them
to a relay under test directly affect test results. Prefault
voltage and current are also a very important factor. The
decaying dc offset is considered as well. Test results for five
different relays using this new method are presented in this
paper. The results demonstrate practical benefits of the test
method.