Title of article :
Insulation characteristics of GIS spacer for very fast transient overvoltage
Author/Authors :
Okabe، نويسنده , , S.، نويسنده , , Koto، نويسنده , , M.، نويسنده , , Endo، نويسنده , , F.، نويسنده , , Kobayashi، نويسنده , , K.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
9
From page :
210
To page :
218
Abstract :
V-t characteristics of spacer surfaces for VFT were investigated under particle contaminated conditions. V-t characteristics for VFT were measured with the particle length, oscillation frequency, amplitude, and damping factor of VFT waveform as parameters. Differences in V-t characteristics for VFT due to variation of oscillation frequency, amplitude, and damping factor were small. Further, they were compared with V-t characteristics for lightning impulse. The dielectric strength of spacer surfaces for VFT was found to be at least equivalent to the dielectric strength for lightning impulse.