Title of article :
Investigations of an EHV autotransformer tested with open and arrester terminated terminals
Author/Authors :
Seitlinger، نويسنده , , W.P.، نويسنده , , Foschum، نويسنده , , H.، نويسنده , , Wagenaar، نويسنده , , L.B.، نويسنده , , Fleeman، Eugene L نويسنده , , J.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
11
From page :
312
To page :
322
Abstract :
The Special Termination Lightning Impulse test was devised to insure that transformers are adequately designed for service conditions not presently covered by standard test procedures. Analytic studies and factory fests were made on an EHV transformer to show effects of this test on a particular design. Calculations predicted terminal and internal voltage responses to the new test and were verified by good correlation with the tests. Analysis of internal voltages indicate that the new test is meaningful for this particular transformer. Examination of terminal responses indicate that the clamping action of the arrester prolongs the voltage crest at the non-impulsed terminals.
Keywords :
InsulationCoordination , impulse testing , EHV Transformers , Arresters.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399080
Link To Document :
بازگشت