• Title of article

    Calculation of HVDC converter noncharacteristic harmonics using digital time-domain simulation method

  • Author/Authors

    Sarshar، نويسنده , , A.، نويسنده , , Iravani، نويسنده , , M.R.، نويسنده , , Li، نويسنده , , J.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    10
  • From page
    335
  • To page
    344
  • Abstract
    In this paper, noncharacteristic harmonics of an HVdc converter station are calculated based on the use of digital time-domain simulation methods. An enhanced version of the Electromagnetic Transients Program (EMTP) is used for the studies. The noncharacteristic harmonics of interest are (1) the dc side triplen harmonics, and (2) the ac side second harmonic. Impacts of loading conditions, neutral filter, and converter firing angle on the dc side triplen harmonics are discussed. Effects of ac side network parameters, static VAR compensator (SVC), transformer half-cycle saturation, and Geomagnetically Induced Current (GIC) on the ac side second harmonic instability are also presented. This paper concludes that the digital time-domain simulation method provides significant flexibility for accurate prediction of (1) generation mechanism, and (2) adverse impacts of HVdc noncharacteristic harmonics.
  • Keywords
    TriplenHarmonics , Second Harmonic Instability , HVDC-ACInteraction , Transformer Half-Cycle Saturation , GIC. , Noncharacteristic Harmonics
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1996
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    399083