Author/Authors :
Fukawa، نويسنده , , M.، نويسنده , , Kawai، نويسنده , , T.، نويسنده , , Okano، نويسنده , , Y.، نويسنده , , Sakuma، نويسنده , , S.، نويسنده , , Asai، نويسنده , , S.، نويسنده , , Yoshihide Kanaoka، نويسنده , , M.، نويسنده , , Yamanouchi، نويسنده , , H.، نويسنده ,
Abstract :
500-kV XLPE-insulated cable with an insulation
thickness of 27 nun has been developed for longdistance
transmission lines. Basic studies ion 500-kV
XLPE cable have shown that contaminants in the insulation
may be the factor determining electrical performance,
This hypothesis is justified by the good correlation
obtained between statistical estimations of the
size of the largest contaminant in the insulation and
the electrical characteristics of full-sized cables.
Voltage-withstand and long-term tests have confirmed
the design values for minimum breakdown stress, for AC
and impulse voltage, and for the degradatioin coefficients.
Keywords :
500 kV , XLPE cable , minimum insulation breakdown strength , designstress , performance-determiningfactor