Author/Authors :
Uchida، نويسنده , , K.، نويسنده , , Kobayashi، نويسنده , , S.، نويسنده , , Kawashima، نويسنده , , T.، نويسنده , , Tanaka، نويسنده , , H.، نويسنده , , Sakuma، نويسنده , , S.، نويسنده , , Hirotsu، نويسنده , , K.، نويسنده , , Inoue، نويسنده , , H.، نويسنده ,
Abstract :
This paper is a report on the results of a basic study of testing
methods to replace the dc after laying test that is presently most frequently used
as an after laying test for XLPE cable lines. Chosen as the alternative
waveforms for dc voltage were damped oscillating wave (OSW) and very-lowfrequency
wave (VLF) voltage. Experiments were conducted on the ability to
detect various types of lme defects under these voltages. It was found that
these alternative waveforms are promising as after laying teʹst voltage
waveforms to replace dc and that greater defect detection ability can be
achieved by combining them when conducting tests.