Title of article :
Model system tests on a new numeric method of power system frequency measurement
Author/Authors :
Moore، نويسنده , , P.J.، نويسنده , , Carranza، نويسنده , , R.D.، نويسنده , , Johns، نويسنده , , A.T.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
A numeric technique for the evaluation of power
system frequency has been implemented on a TMS320C31
digital signal processor. The frequency measuring
equipment has been tested on programmable relay testing
equipment, using known reference signals, and on a
micromachine based power system simulator. The results
show the frequency measuring equipment gives fast and
accurate measurement under both steady-state and
dynamic conditions. The response of the equipment to
instantaneous changes in phase and amplitude is found to
be undesirable if the algorithm is to be applied to
frequency measuring protection relays.
Keywords :
Frequency measurement , Digital signal processing
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :