Title of article :
A fast and accurate analysis of grounding resistance of a driven rodbed in a two-layer soil
Author/Authors :
Elsherbiny، نويسنده , , M.M.، نويسنده , , Chow، نويسنده , , Y.L.، نويسنده , , Salama، نويسنده , , M.M.A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Pages :
7
From page :
808
To page :
814
Abstract :
A moment method of the Galerkin (variational) approach is applied to analyze the grounding resistances of driven rodbed of various configurations. Using this approach the resistance of a rodbed of N rods in two-layer soil requires only a mauix size of 2NX2N (two segments for each rod). The error m the calculated resistance is less than 4% compared to the resistance calculated by point matching moment method of large number of segmentation for each rod. The efficiency due to a small maw with high accuracy allows an extensive parametric analysis of the rodbed. The study shows that a precise placement of the rods is not necessary to maintain a given resistance.
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
1996
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Record number :
399130
Link To Document :
بازگشت