A 6.6 kV pin-post insulator, incorporating ZnO
varistors, has been developed in order to reduce line faults caused
by direct lightning strikes, thereby reducing and simplifving
maintenance work on distribution systems. The developed
insulators are interchangeable with conventional pin insulators and
can withstand internal fault currents twice upon their failures. The
simulated results regarding the response of the developed
insulators to direct lightning strikes on an overhead ground wire
agreed well with the experimental results. Simulation studies also
revealed that installing the developed insulators on every two poles
reduces the line-fault rate of present distribution lines in case of
direct lightning strikes by 33%, while installing them on every pole
reduces the rate by 97.5% or about 1/40 of the original value.
Keywords :
Lightning protection , direct lightning strike , surge arrester , distribution line , EMTP , insulator