Author/Authors :
Peelo، نويسنده , , D.F.، نويسنده , , Polovick، نويسنده , , G.S.، نويسنده , , Sawada، نويسنده , , J.H.، نويسنده , , Diamanti، نويسنده , , P.، نويسنده , , M. PRESTA، نويسنده , , R.، نويسنده , , Sarshar، نويسنده , , A.، نويسنده , , Beauchemin، نويسنده , , R.، نويسنده ,
Abstract :
B.C. Hydro and Hydro-Quebec utilize current
limiting reactors on medium voltage distribution feeders to limit
the magnitude of fault current. The reactors make a significant
contribution to the severity of the transient recovery voltage
experienced by feeder and bus circuit breakers on clearing
feeder faults. Based on the conclusions of an investigation of
actual circuit breaker failures while performing this duty, the
mitigation of the transient recovery voltage associated with the
reactors is described.