Author/Authors :
Nakadate، نويسنده , , M.، نويسنده , , Toda، نويسنده , , K.، نويسنده , , Sato، نويسنده , , K.، نويسنده , , Biswas، نويسنده , , D.، نويسنده , , Nakagawa، نويسنده , , C.، نويسنده , , Yanari، نويسنده , , T.، نويسنده ,
Abstract :
We have developed the gas-cooling system of a
275 kV, 300 MVA class gas-insulated transformer. In our study
model experiments in which gas flow was substituted by water
flow equivalently and 2-dimensional numerical flow analyses
and network analyses were conducted. In this paper the outline
of the development and optimization condition to get high cooling
performance in SF6 gas-disc winding system of the transformer
are presented.