A thyristor controlled ground fault current limiting
system (TGCL) was proposed to prevent one-line ground fault
current rises due to increased capacitance to ground. Basic
components of the TGCL are a main ground fault current
limiter, which rapidly adjusts a compensating reactor level for
the capacitance to ground, and the TGCLʹs controller. Control
is ensured by an in-phase control method for zero-phase
sequence voltage and current. The method determines the
direction of ground faults and the compensating reactor level.
The fast control which can be realized shows the TGCL is a
valuable protecting system for high ground fault current
distribution systems.
Keywords :
Ground Fault , Current Limiter , Thyristor Control , FaultProtection , Distribution System.