Matsumoto، نويسنده , , Y.، نويسنده , , Sakuma، نويسنده , , O.، نويسنده , , Shinjo، نويسنده , , K.، نويسنده , , Saiki، نويسنده , , M.، نويسنده , , Wakai، نويسنده , , T.، نويسنده , , Sakai، نويسنده , , T.، نويسنده , , Nagasaka، نويسنده , , H.، نويسنده , , Motoyama، نويسنده , , H.، نويسنده , , Ishii، نويسنده , , M.، نويسنده ,
Abstract :
Measurement of lightning surges caused by
natural or rocket-triggered lightning strokes has been
carried out on a 275kV test transmission line since 1987.
In November 1993, lightning currents at the tower top,
the ground wires, the tower legs and the transmission line
arresters, along with the voltages across the insulator
strings were measured simultaneously four times. One of
the four flashes was natural lightning, and its peak value
was +132kA. In this case, the arresters operated, and the
insulator voltages where the arresters were equipped were
controlled properly.
The result of a multi-phase analysis by EMTP agreed
well with the measured waveforms.