An application study for sizing and rating controlled and conventional series compensation
Author/Authors
Kosterev، نويسنده , , D.N.، نويسنده , , Mittelstadt، نويسنده , , W.A.، نويسنده , , Mohler، نويسنده , , R.R.، نويسنده , , Kolodziej، نويسنده , , W.J.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
7
From page
1105
To page
1111
Abstract
A step by step method for determining controlled
and conventional series compensation requirements
is developed. The Montana 500kV transmission system is
taken as an example in this study. A base transfer rating
of 2200MW for the system already exists, and it is assumed
that as its power loading increases, controlled series
compensation is needed to reinforce the system. Combination
of conventional and thyristor-controlled series compensators
(TCSCs) is considered as a means of increasing
the system transfer capability. Powerflow and transient
stability studies are performed to rate and size the series
compensators. The TCSC reactance control capabilities
are established for steady-state and transient conditions.
An installation sequence is developed relating facility requirements
to system loading.
Keywords
transmission system planning , FACTS. , Series Capacitors , thyristor-controlled seriescompensation